Fuji

I/P & P/I Converters

  Description
These 2-wire (loop-powered) I/P transmitters accept a
current signal (such as 4-20mA) from a DCS, PLC or
PC-based control system. They convert the current
signal to a pneumatic signal (3-15psig, 0.2-1bar,
20-100kPa, etc.) to provide precise, proportional
control of valves, actuators and other pneumaticallycontrolled
devices.
The economical IPH2 (NEMA 4X) is
watertight, dust-protected, and resistant to corrosion
and chemicals. In addition to meeting NEMA 4X
requirements, the IPX2 can be installed in explosionproof
environments.
Both units are available with an optional coalescing
filter/regulator that combines an air filter and miniature
supply line regulator with a pressure gauge that reads
in both psig and bars.
     
Specification  
  • PERFORMANCE
    Accuracy: <±0.25% of span including the combined effect of linearity, hysteresis
    and repeatability (between 0 and 3psig output, error will not exceed ±1.0% of span)
    Stability: Not to degrade from stated accuracy for six months
    Step Response: <0.2 seconds into 100ml load (6 in3) from 10% to 90% of span; Not guaranteed below 3psig output
    Supply Pressure Effect: Negligible from 20-40psig, steady pressure
    Air Capacity: 5.0SCFM minimum (20psig supply, 0psig output)
    Relief Capacity: 2.5SCFM minimum (15psig output)
    Air Supply: Instrument air only, 20-40psig. (Must be 5psig greater than maximum output)
    Gas Supply with -NG1 or -NG2 Option: Same
    cleanliness as instrument air. H2S not to exceed 20ppm
    Air Consumption (Dead-ended): At 3psig output, 20psig supply, consumes 0.08SCFM (0.14m3/hr), maximum; At 15psig output, 20psig supply, consumes
    0.10SCFM (0.17m3/hr), maximum; At 15 psig output, 40psig supply, consumes
    0.15SCFM (0.26m3/hr), maximum; At 30psig output, 40psig supply, consumes
    0.17SCFM (0.29m3/hr), maximum
    Maximum Input: 80psig without damage for units with output pressure rating of
    >15psig; 45psig without damage for units with output press 15psig
    Voltage Drop: 5V, maximum
    Mounting Position Effect: Negligible, unit can be mounted in any position; Should be mounted upright or horizontal to keep water out if it is not in a dry environment
  • AMBIENT CONDITIONS
    Operating & Storage Range: -40°C to +85°C (-40°F to +185°F)
    Ambient Temperature Effect: <±0.025% of span/ °C, maximum from
    -20°C to 80°C; <±0.1% of span/°C, maximum
    RFI/EMI Effect: <±0.25% of span change at in field strengths of 10V/m@ frequencies of 20-1000MHz
    Shock and Vibration Effect: Meets SAMA PMC 31.1 as detailed in the field mounted
    category and rated as follows: 5-15Hz, 2mm peakto- peak; 15-150Hz, 1g;
    150-2000Hz, 0.5g
    Relative Humidity: 0-100%, non-condensing
    Zero & Span: Screw adjusts zero or span by ±10% minimum, non-interactive
    IPH2: 1.14kg (2.5 lbs)
    IPX2: 2.0kg (4.4 lbs)