Fuji
DP Temperature Transmitters
  Features
1. High accuracy
0.1% accuracy is the standard feature . Fuji's microcapacitance
silicon sensor assures this feature for all
elevated or suppressed calibration ranges without
additional adjustment.
2. Minimum inventory
Electronics unit, local indicators and electronics housing
are interchangeable among all FCX-CII models. Process
cover including bolts and nuts are common for all DP
and flow transmitters.
3. Fuji/HARTTM bilingual communication protocol and
FOUNDATIONTM Fieldbus and ProfibusTM compatibility
FCX-CII series transmitter offers bilingual communication
to speak both Fuji proprietary protocol and HARTTM.
Any HARTTM compatible devices can communicate with
FCX-CII.
Further, by upgrading electronics FOUNDATIONTM
Fieldbus and ProfibusTM are also available.
4. Application flexibility
Example features that render the FCX-CII suitable for
almost any process applications includes :
- Analog indicator at either the electronics side or terminal
side
- Full range of hazardous location approvals
- Built-in RFI filter and lightning arrester
- 5 digits LCD meter
5. Programmable output Linearisation Function
In addition to linear and square root, output signal is
freely programmable.
6. Burnout current flexibility (Under Scale : 3,2 to 3,8mA,
Over scale : 20,8 to 21,6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit), reliability of dry
calibration without r
     
Technical Specification  
  • Functional specifications
    Type :
    FKK : Smart, 4-20mA dc + Fuji/HartTM digital signal
    FDK : FOUNDATIONTM Fieldbus & ProfibusTM
    Service :
    Liquid, gas or vapour
    Overrage limit : To maximum static pressure limit.
    Output signal :
    4 to 20mA DC (linear or square root) with digital signal
    superimposed on the 4 to 20mA signal
    Digital signal based on FOUNDATIONTM Fieldbus or
    ProfibusTM.
    Power supply :
    Transmitter operates on 10.5V to 45V DC at
    transmitter terminals.
    10.5V to 32V DC for the units with optional arrester.
    Hazardous locations :
    Designed to meet international intrinsic safety and
    flameproof (explosionproof) standards.
    Please consult the code symbols some pages further
    on, to know the different types of approvals (digit 10).
    Consult FUJI for status.
    Zero/span adjustment :
    Zero and span are adjustable by hand held
    communicator in HartTM or Fuji protocol.Local
    adjustment of zero and span are possible from outside
    screw on the electronic housing.
    Damping : adjustable from HHC.
    A damping of the output signal is possible between 0
    and 32 sec with the hand held communicator HHC.
    Local adjustment possibilities with LCD indicator (refer
    to optional indicator).
    Zero elevation / suppression :
    Selectable with the hand held communicator (HHC) or
    from outside screw on the electronic housing.
    Normal / reverse action :
    Programmable with hand held communicator (HHC).
    Indicator :
    A plug-in analog indicator can be mounted on the
    electronics unit or the terminal block.
    The local LCD indicator (5 digits) is assembled on the
    electronics unit.
    Additional local adjustment facilities are possible by the
    integrated switches in the LCD indicator :
    - "Local/comm" switch gives the possibilities to
    make local adjustments of zero/span, damping or
    to configure the transmitter with a hand held
    communicator.
    - The "mode" switch with 7 positions gives local
    adjustment possibilities for zero/span, 4/20mA,
    enable or inhibit the local adjustments.
    - Local damping adjustment is possible via the
    "damp" switch.
    Burnout direction: Selected from HHC
    If self-diagnostic detect transmitter failure, the analog
    signal will be driven to eighter "Output Hold", "Output
    Overscale" or "Output Underscale" modes.
    "Output Hold" :
    Output signal is hold as the value just before the
    failure happens.
    "Output Overscale" : approx. 21,6 mA
    Adjustable within the range 20,8 mA to 21,6 mA
    from the HHC.
    "Output Underscale" : approx. 3,8 mA
    Adjustable within the range 3,2 mA to 3,8 mA from
    the HHC.