Controllers |
 |
|
Overview |
|
|
|
|
|
|
|
|
|
|
|
This product has been designed, developed and manufactured for
general-purpose application in machinery and equipment.
Accordingly, when used in applications outlined below, special care
should be taken to implement a fail-safe and/or redundant design
concept as well as a periodic maintenance program.
• Safety devices for plant worker protection
• Start/stop control devices for transportation and material
handling machines
• Aeronautical/aerospace machines
• Control devices for nuclear reactors
Never use this product in applications where human safety may be
put at risk. |
| |
|
|
| Technical Specification |
|
|
- PV Input
Thermocouple: K,J,E,T,R,S,B,N (JIS C1602-1995)
PL II (Engelhard Industries Data (ITS90))
WRe5-26 (ASTM E988-96(Reapproved
2002))
DIN U,DIN L (DIN 43710-1985)
Resistance temperature detector (RTD):
Pt100 (JIS C1604-1997)
JPt100 (JIS C1604-1989)
DC voltage: 0 to 1V, 1 to 5V, 0 to 5V, 0 to 10V
DC current: 0 to 20mA, 4 to 20mA
Sampling cycle: 500ms
Accuracy : ±0.5%FS±1digit, ±1%FS±1digit for a negative area of the
thermocouple (at ambient temperature
23±2°C)
|
- Digital input
Input type : Dry contact or open collector
Allowable ON contact resistance : Max.250Ω
Allowable OFF contact resistance : Min.100kΩ
Allowable ON voltage : Max.1.0V
Terminal current (ON ) : Approx.7.5mA in case of short circuit
Approx.5.0mA in case of contact resistance
250Ω
Minimum hold time : 1s or more
|
- Current transformer input
Number of input points: 2 points
Input object: Current transformer with 100 to 4,000 turns
(availability is by 100-turn units)
Optional unit Model No.: QN206A
(800 turns, hole diameter: 5.8 mm)
Optional unit Model No.: QN212A
(800 turns, hole diameter: 12mm)
Current measurement
lower limit: 0.4Aac (800 turns, 1 time)
Formula; Number of turns ÷ (2000 x number
of power wire loops)
Current measurement
upper limit: 50.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of
power wire loops)
Allowable measured current: 70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of
power wire loops) x 1.4
Display range lower limit: 0.0Aac
Display range upper limit: 70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of
power wire loops) x 1.4
Display accuracy: ±5%FS
Display resolution: 0.1Aac
|
- Control Output
• Relay output
Contact rating : NO side 250Vac/30Vdc, 3A (resistive load)
NC side 250Vac/30Vdc, 1A (resistive load)
Life : NO side Min. 50,000 operations
NC side Min. 100,000 operations
Min. switching specifications : 5V, 100mA
Min. ON time / OFF time : 250ms
• Voltage pulse output (for SSR drive)
Open circuit voltage : 19Vdc±15%
Internal resistance : 82Ω±0.5%
Allowable current : Max. 24mAdc
Min. OFF time / ON time : 1ms (Time proportional cycle time < 10s)
250ms (Time proportional cycle time ≥ 10s)
• Current output
Output type : 0 to 20mAdc or 4 to 20mAdc current output
Allowable load resistance : Max.600Ω
Output accuracy : ±0.5%FS (at ambient temperature 23±2°C)
±1%FS at 0 to 1mA
|
- Event relay outputs (ev1 to 3)
Contact rating : 250Vac/30Vdc 2A (resistive load)
Life : Min. 100,000 operations
Min. switching specification : 5V, 10mA (Reference value)
|
- RS-485 communication
Transmission line : 3-wire system
Transmission speed : 4800, 9600, 19200, 38400bps
Communication protocol : CPL and MODBUS conforming
Terminating resistor : Do not connect a terminating resistor.
|
- Environmental condition
• Operating conditions
Ambient temperature : 0 to 50°C (Gang-mounting: 0 to 40°C)
Ambient humidity : 10 to 90%RH (non-condensing)
Power supply voltage : AC Model
85 to 264Vac, 50/60Hz±2Hz
(Rated power voltage 100 to 240Vac 50/60Hz)
DC Model
21.6 to 26.4Vac, 50/60Hz±2Hz
21.6 to 52.8Vdc
(Rated power voltage 24Vac 50/60Hz,
24 to 48 Vdc)
• Transport conditions
Ambient temperature : –20 to +70°C
Ambient humidity : 10 to 95%RH (non-condensing)
|
- Other specifications
Degrees of protection : Case front side IP66 /NEMA 4X equivalent
(Only for stand-alone mounting on a panel
when an attached gasket is used. )
Power consumption : AC Model
Max. 12VA (100Vac:8VA, 264Vac:12VA)
(6VA for 100Vac and 9VA for 264Vac to
our company SDC10 equivalent function)
DC Model
Max. 7VA (24Vac)
Max. 5W (24 to 48Vdc)
Non-detected power failure time : Max. 20ms (AC model)
No power failure allowed (DC model)
Altitude : Max. 2000m
Mass : Approx.150g (with mounting bracket) at
panel mount type
Approx.200g (with socket) at socket mount
type
Terminal screw tightening torque : 0.4 to 0.6N·m
Applicable standards : EN61010-1, EN61326
Over-voltage category : Category II (IEC60364-4-443, IEC60664-1)
Allowable pollution degree : Pollution degree 2
|
|
|