Eurotherm
Process and Temperature Controllers
  Overview
The innovative range of 3200 controllers offer precision control of temperature and other process variables together with a host of advanced features not normally found in this class of controller.
The emphasis is on ease of use. A simple ‘Quick Start’ code is used to configure all the functions essential for controlling your process. This includes input sensor type, measurement range, control options, and alarms, making ‘Out the Box’ operation truly achievable. In operator mode
every parameter has a scrolling text message describing its function and is available in English, German, French, Spanish or Italian. More advanced features are configured using iTools, a PC based configuration wizard which
is an easy to use and instructive guide to all the functions in the controller.
     
Technical Specification  
  • General
    Environmental performance
    Temperature limits Operation: 0 to 55°C
    Storage: -10 to 70°C
    Humidity limits Operation: 5 to 90% RH non condensing
    Storage: 5 to 90% RH non condensing
    Panel sealing: IP65, Nema 4X
    Shock: BS EN61010
    Vibration: 2g peak, 10 to 150Hz
    Altitude: <2000 metres
    Atmospheres: Not suitable for use in explosive or
    corrosive atmosphere
    Electromagnetic compatibility (EMC)
    Emissions and immunity: BS EN61326
    Electrical safety
    (BS EN61010): Installation cat. II; Pollution degree 2
    INSTALLATION CATEGORY II
    The rated impulse voltage for equipment on nominal 230V mains is 2500V.
    POLLUTION DEGREE 2
    Normally, only non-conductive pollution occurs. Occasionally, however, a
    temporary conductivity caused by condensation shall be expected
    Physical
    Panel mounting 3216: 1/16 DIN
    3208: 1/8 DIN
    3204: 1/4 DIN
    32h8: 1/8 DIN, horizontal
    Weight 3216: 250g
    3208: 350g
    3204: 420g
    32h8: 350g
    Panel cut-out dimensions 3216: 45W x 45Hmm
    3208: 45W x 92Hmm
    3204: 92W x 92Hmm
    32h8: 92W x 45Hmm
    Panel depth All: 90mm
    Operator interface
    Type: LCD TN with backlight
    Main PV display: 4 digits, green
    Lower display 3216, 3208, 3204: 5 character starburst, green
    32h8: 9 character starburst, green
    Status beacons: Units, outputs, alarms, active setpoint
    Power requirements
    3216: 100 to 240Vac, –15%, +10%,
    48 to 62 Hz, max 6W
    24Vac, -15%, +10%.
    24Vdc, -15% +20% ±5% ripple voltage
    max 6W
    3208/h8/04: 100 to 240Vac, –15%, +10%,
    48 to 62 Hz, max 8W
    24Vac, -15%, +10%.
    24Vdc -15% +20% ±5% ripple voltage
    max 8W
    Approvals
    CE, cUL listed (file E57766), Gost,
    DIN 3440 (3216 only)
    Suitable for use in Nadcap and
    AMS2750D applications under Systems
    Accuracy Test calibration conditions
    Transmitter PSU (not 3216)
    Rating: 24Vdc, >28mA, <33mA
    Isolation: 264Vac double insulated
  • Communications
    Serial communications option:
    Protocol: Modbus RTU slave
    Modbus RTU Master broadcast
    (1 parameter)
    Isolation: 264Vac, double insulated
    Transmission standard: EIA232 or EIA485 (2 wire)
    EIA485(4 wire) on 3216 only
  • Process variable input
    Calibration accuracy: <±0.25% of reading ±1LSD (1)
    Sample rate: 4Hz(250ms)
    Isolation: 264Vac double insulation from the PSU
    and communication
    Resolution (μV): <0.5μV with 1.6sec filter
    Resolution (effective bits): >17 bits
    Linearisation accuracy: < 0.1% of reading
    Drift with temperature: <50ppm (typical) <100ppm (worst case)
    Common mode rejection: 48-62Hz, >-120db
    Series mode rejection: 48-62Hz, >-93dB
    Input impedance: 100MΩ
    Cold junction compensation: >30:1 rejection of ambient change
    External cold junction: Reference of 0°C
    Cold junction accuracy: <±1°C at 25°C ambient
    Linear(process) input range: -10 to 80mV, 0 to 10V with
    100KΩ/806Ω external divider module
    Thermocouple types: K, J, N, R, S, B, L, T, C, custom
    download (2)
    Resistance thermometer types: 3-wire Pt100 DIN 43760
    Bulb current: 0.2mA
    Lead compensation: No error for 22 ohms in all leads
    Input filter: Off to 59.9s
    Zero offset: User adjustable over full range
    User calibration: 2-point gain & offset
  • AA relay
    Type: Form C (changeover)
    Rating: Min 100mA@12Vdc, max 2A@264Vac
    resistive
    Functions: Control outputs, alarms, events
  • Current transformer input
    Input range: 0-50mA rms, 48/62Hz. 10Ω burden
    resistor fitted inside module
    Calibration accuracy: <1% of reading (Typical),
    <4% of reading (Worst case)
    Isolation: By using external CT
    Input impedance: <20Ω
    Measurement scaling: 10, 25, 50 or 100 Amps
    Functions: Partial load failure, SSR fault
  • Digital input (DigIn A/B, B not on 3216)
    Contact closure: Open >600Ω, closed <300Ω
    Input current: <13mA
    Isolation: None from PV or system
    264Vac double insulated from PSU and
    communications
    Functions: Includes alarm acknowledge, SP2 select,
    manual keylock, timer functions, standby
    select, RSP select
  • Logic I/O module
    Output
    Rating: ON 12Vdc@<44mA,
    OFF <300mV@100μA
    Isolation: None from PV or system.
    264Vac double insulated from PSU and
    communications
    Functions: Control outputs, alarms, events
    Digital input
    Contact closure: Open >500Ω, closed <150Ω
    Isolation: None from PV or system
    264Vac double insulated from PSU and
    communications
    Functions: Includes alarm acknowledge, SP2
    select, manual, keylock, timer functions,
    standby select, RSP select
  • Relay output channels
    Type: Form A (normally open)
    Rating: Min 100mA@12vdc, max 2A@264Vac
    resistive
    Functions: Control outputs, alarms, events
  • Triac output
    Rating: 0.75A (rms) 30 to 264V(rms) resistive
    load
    Isolation: 264Vac double insulated
    Functions: Control outputs, alarms, events
  • Analogue output (3)
    OP1, OP2
    Rating: 0-20mA into <500Ω
    Accuracy: ± (<1% of Reading + <100μA)
    Resolution: 13.5 bits
    Isolation: 264Vac double insulated from PSU and
    communications
    Module code C provides full 264Vac
    double isolated
    Functions: Control outputs, retransmission
    OP 3 (not on 3216)
    Rating: 0-20mA into <500Ω
    Accuracy: ±(<0.25% of Reading + <50μA)
    Resolution: 13.6 bits
    Isolation: 264Vac double insulated
    Functions: Control outputs, retransmission
  • Remote setpoint input
    Calibration accuracy: <±0.25% or reading ±1LSD
    Sample rate: 4Hz (250ms)
    Isolation: 264Vac double insulation from instrument
    Resolution: <0.5mV (for 0-10V) or <2μA (for 4-20mA)
    Resolution (effective bits): >14bits
    Drift with temperature: <50ppm (typical) <150ppm (worst case)
    Common mode refection: 48-62Hz, >-120dB
    Series mode rejection: 48-62Hz, >-90dB
    Input impedance: Voltage: 223KOhm and Current: 2R49
    Normal input range: 0 to 10V and 4 to 20mA
    Max input range: -1V to 11V and 3.36mA to 20.96mA
  • Software features
    Control
    Number of loops: 1
    Loop update 250ms
    Control types: PID, ON/OFF, VP
    Cooling types: Linear, fan, oil, water
    Modes: Auto, manual, standby, forced manual
    Overshoot inhibition: High, low
    Alarms
    Number: 4
    Type: Absolute high & low, deviation high, low
    or band, rate of change
    Latching: Auto or manual latching, non-latching,
    event only
    Output assignment: Up to four conditions can be assigned to
    one output
    Other status outputs
    Functions: Including sensor break, manual mode,
    timer status, loop break, heater
    diagnostics, program event
    Output assignment: Up to four conditions can be assigned to
    one output
    Setpoint programmer
    Program function: 1 program x 8 segments with 1 event
    output (4)
    Start mode: Servo from PV or SP
    Power fail recovery: Continue at SP or Ramp back from PV
    Guaranteed soak: Inhibits dwell timing until PV within
    limits
    Timer
    Modes Dwell when setpoint reached
    Delayed control action,
    Soft start limits power below PV threshold
    Current monitor
    Alarm types: Partial load failure, over current, SSR
    short circuit, SSR open circuit
    Indication type: Numerical or ammeter
    Custom messages
    Number: 15 scrolling text messages
    No of characters: 127 characters per message max
    Languages: English, German, French, Spanish, Italian
    Selection: Active on any parameter status using
    conditional command
    Recipes
    Number: 5 recipes with 38 parameters
    Selection: HMI interface, communications or
    digital IO